    Product Description

    Product Selection

    Example: KLD-T-T-2000A/5P: Cast-resin busbar, resin-encapsulated, copper busbar conductor, rated current 2000A, three-phase five-wire system.

     

    Scope of application

    The resin-encapsulated, fully enclosed busbar system has a rated current ranging from 100A to 8000A, a rated frequency of 50–60Hz, a rated operating voltage of 380V, and a rated insulation voltage of 660V. Its enclosure boasts the highest protection rating of IP68, and it features fire resistance, water resistance, and corrosion resistance. Therefore, it can be widely used in:

    1. High-rise buildings where firefighting is difficult;

    2. Places with harsh working conditions, such as those involving explosion hazards or corrosive liquids;

    3. Outdoor areas, trenches, and other locations with high humidity or the potential for flooding.

     

    Product Features

    1. Resin-encapsulated fully enclosed busbar trunking systems shall use copper, aluminum, and copper-aluminum composite conductor materials with high electrical conductivity.

    2. The resin-encapsulated, fully enclosed busbar system uses a specially formulated composite resin mixed with precisely selected, quantitatively measured additives to create a high-performance insulating material that directly encapsulates and seals the copper busbars. There are no air gaps, no smoke and fume effects, and short circuits cannot be caused by burrs on the busbars or overloads.

    3. Corrosion Resistance: Resistant to corrosion by a wide variety of chemicals, allowing for long-term use in both indoor and outdoor polluted environments.

    4. Water Resistance: The enclosure has an IP68 protection rating, allowing it to operate continuously underwater. It can be directly laid in cable trenches (without the need for any additional protective devices) and can even be buried underground.

    5. Mechanical Performance: Able to withstand strong mechanical impacts, ensuring safe use.

     

    Main Technical Parameters

    1. Rated current: 100A to 8000A; rated frequency: 50 to 60Hz; rated operating voltage: 380V; rated insulation voltage: 660V.

    2. The busbar trunking system can withstand a power-frequency withstand voltage of 3750V for 1 minute without any breakdown or flashover phenomena.

    3. With an IP68 protection rating, it features excellent air-tightness and water-tightness.

    4. Temperature rise not exceeding 55K.

    5. Fire rating F120.

    6. Fire resistance: 950°C / 90 mm.

    7. Wide specification range: 100A–8000A.

    8. High mechanical strength, capable of withstanding an impact force of 6 joules.

     

    Install the attachment

    Vertical mounting clamp and vertical mounting beam

    When busbar trunking systems are installed vertically, vertical mounting clamps must be used. These clamps are suitable for busbar trunking systems of all current ratings.

    Horizontally mounted pressure plate and horizontally mounted beam

    When busbar trunking is installed horizontally, a horizontal mounting clamp must be used. It is suitable for busbar trunking of all current ratings. The dimensions of the horizontal mounting beam are related to the current rating in amperes.

    Note:

    1. All dimensions are in mm.

    2. All dimensions provided are for standard products. If you require custom product dimensions, please contact our engineers.

    3. The horizontal presser and side-mounted presser are provided by the factory.

     

    Middle fixed bracket

    When busbar trunking is installed vertically on floors exceeding 3.5 meters in height, use intermediate fixing brackets. These intermediate fixing brackets are mounted on the walls between two floors to prevent horizontal movement of the busbar trunking and are suitable for busbar trunking of all current ratings.

    Note:

    1. L1 and L2 are customized based on different engineering requirements, while the remaining dimensions are used for standard products.

     

    Spring bracket

    Spring supports must be used on each floor to support the weight of the vertically installed busbar trunking on that floor.

    The spring bracket is connected to the busbar trunking system via bolts.

    The number of spring supports varies depending on the amperage rating of the busbar trunking system. Please refer to Table 22-1.

    Attachment:

    1. Spring support

    2. Hex bolt

    3. Double-head bolt

    4. Spring

    5. Gasket

    6. Channel steel base (to be provided by the user)

    Current rating

    Number of springs

    250-800

    2

    1000-2500

    4

    3150-5000

    6

    Table 22-1

    Note:

    1. All dimensions are in mm.

    2. All dimensions provided are for standard products. For customized products, please contact our engineers for the relevant dimensions.

     

    Install

    Minimum distance required for installation

    Minimum distance reserved for installing the plug-in box

    When busbar trunking is installed horizontally or vertically close to a wall, it is essential to reserve a certain dimension for the installation of plug-in boxes. Please refer to Table 24-1.

    Minimum reserved distance when busbar trunking is equipped with plug-in boxes

    Plug-in box current rating (A)

    100

    250

    400

    630

    800

    1000

    L(mm)

    150

    195

    210

    230

    260

    300

    Form 24-1

    Horizontal installation

    1. Horizontal wall-mounted installation

    See the figure below for the dimensions of the pre-reserved holes for horizontal wall-mounted installation:

    2. Horizontal ceiling installation

    When installing busbar ceiling supports, pre-drill holes in the floor slab and insert steel expansion bolts (or drill holes on-site for flexible installation) or embed steel components and weld lifting brackets on-site. The spacing between adjacent brackets should generally not exceed 2 meters; if there are special requirements, please specify them when placing your order.

    There are two different forms for horizontal lifting of busbars, as shown in the figure below:

    3. Install horizontally along the wall

    Please pay attention to the straightness of the mounting holes (i.e., ensure that all brackets are installed in a single horizontal plane). Refer to the illustration for the installation method.

    Horizontal wall-mounted units come in both vertical and horizontal versions.

    Vertically installed

    Refer to the drawing for the dimensions of the reserved openings for busbars installed vertically across floor levels. If two or more rows of busbars pass through, the spacing between any two adjacent rows of busbars must be no less than 350 mm.
    See the figure below:

    1. The main installation methods for spring supports are as follows:

    2. Busbar trunking systems installed in shafts should be reinforced at their midsections—generally when the distance between adjacent floors exceeds 3.5 meters or when the customer has special requirements. Angle steel and spring supports are two optional solutions.

    3. The terminals of the busbar trunking system also need to be reinforced, as shown in the figure below:

    4. The reinforcement of the terminal box can be accomplished through the following methods:

    Instructions for Selection and Order

    Instructions for Selection

    The following information must be indicated on the architectural installation drawings and busbar routing diagrams:

    *The model, rated current, and operating voltage level of the busbar trunking system;

    *Is the busbar trunking system plug-in or feed-in?

    * Nature of the power supply and protection level;

    *Busbar trunking installation method, including the installation locations of all accessories and their dimensional constraints;

     

    Order Form

    Project

    Specific content

    Conductor Type

    □ Copper conductor □ Aluminum conductor

    Rated capacity

    □100A □160A □200A 250A □400A □500A □630A □800A □1000A □1250A
    □1600A 2000A 2500A 3150A □4000A □5000A □6300A

    Number of phases and wiring system

    □3P3W L1, L2, L3 □3P4W L1, L2, L3, PEN 100%
    □3P5W L1,L2,L3N100%PE50% □3P5W L1,L2,L3N100%PE100%
    □3P5W L1,L2,L3N200%PE50% □3P5W L1,L2,L3N200%PE100%
    □ The enclosure is 50% grounded (this item must be noted when the enclosure is 50% grounded).

    Phase sequence

    □ Option 1 □ Option 2 □ Option 3 □ Option 4 □ Option 5 □ Option 6 □ Option 7 □ Option 8 □ Other

    Frequency

    □50Hz □60Hz

    Voltage

    □400V □690V

    Protection level

    □IP40 □IP42 □IP54 □IP65 □Other

    Color

    □RAL7000 □RAL7032 □Other

    Product Model

    □ Number of plug-in busbar slots ___ meters □ Number of feed-in busbar slots ___ meters

    Number of plug-in interfaces

    □1 □2 □3 □4 □One side □Both side

    Attachment

    □ Number of L-shaped vertical bends (on the N-phase inner side): ____ □ Number of L-shaped vertical bends (on the N-phase outer side): ____
    □ Number of L-shaped vertical bends (on the N-phase inner side): ____ □ Number of L-shaped vertical bends (on the N-phase outer side): ____
    □ Number of T-shaped vertical bends (on the N-phase inner side): ____ □ Number of T-shaped vertical bends (on the N-phase outer side): ____
    □ Number of T-shaped vertical bends (on the N-phase inner side): ____ □ Number of T-shaped vertical bends (on the N-phase outer side): ____
    □ Number of terminals ___ units □ Number of busbars at the starting end ___ units
    □ Number of variable-capacitance busbars: ___ units □ Number of expansion busbars: ____ units □ Number of phase-shifting busbars: ___ units

    Plug-in box

    □ Isolating switch + fuse □ MCCB □ Rotary handle operation □ Crank-type operation

    Rated current

    _A_ only _A_ only _A_ only _A_ only _A_ only _A_ only
    _A_ only _A_ only _A_ only _A_ only _A_ only _A_ only

    Short-circuit current

     

    Bracket

    □ Horizontal ___ units □ Vertical ___ units

    Delivery date

     

     

    Mode of transportation

     

     

    Destination address

     

     

    Contact Information

     

     

    Special requirements

     

     